SCADA Supervisory Control & Data Acquisition
Water Distribution Mimic Diagram
Sourced from a 400-foot deep well under the pump house, water is initially discharged into Tank 1. A dedicated transfer pump then directs the water through an advanced dual-stage sediment and arsenic filtration system into Tank 2. Following this treatment process, a high-pressure lift pump elevates the purified water to Tanks 3 and 4 at an elevation of 1,030 feet. From this apex, natural gravity efficiently distributes potable water to member residences situated below.
Well Production (WP-01)
6.8 GPM
Filtration Train Pressures
ONLINE · NOMINAL
Sediment (SF-01):
Δ 4.00 PSI
Cartridge Clog Limit:
Clean (4.0 / 50.0 PSI)
Arsenic (AF-01):
Δ 31.80 PSI
Lift Pump (LP-01)
22.5 GPM
Lower Storage (T1 + T2)
ELEV 630 FT
79%
Upper Storage (T3 + T4)
ELEV 1,030 FT
83%
Community Outflow
HOMES ELEV 920 FT
16.8 GPM
Edge Telemetry Ingestion & SQLite Store
Edge Node Push: api/ingest.php · Database: data/telemetry.db (Protected SQLite)
Edge Feed · Live
| Physical Sensor / Node | Telemetry Data Key | Telemetry Reading | Hydraulic Interpretation | Feed State |
|---|---|---|---|---|
| Tank 3 Transducer | tanks/tank3/pressure | 3.46 PSI | ~12,022 Gal (75.1% capacity) | ● Live Stream |
| Tank 4 Transducer | tanks/tank4/pressure | 0.00 PSI | Hardware Sensor Pending Installation | ○ Pending |
| Well Pump (400' Aquifer) | pump/well/pressure | 4.50 PSI | Discharge directly into Tank 1 wellhead | ● Live Stream |
| Sediment Filter Inlet | filters/sediment/in/pressure | 44.00 PSI | Pre-cartridge line pressure from transfer pump | ● Live Stream |
| Sediment Filter Outlet | filters/sediment/out/pressure | 40.00 PSI | Clean Cartridge (ΔP: 4.00 PSI) | ● Live Stream |
| Arsenic Filter Inlet | filters/arsenic/in/pressure | 38.00 PSI | Adsorptive media vessel entrance | ● Live Stream |
| Arsenic Filter Outlet | filters/arsenic/out/pressure | 6.20 PSI | Media Bed Drop (ΔP: 31.80 PSI) → Tank 2 | ● Live Stream |
| High-Pressure Lift Pump | pump/lift/pressure | 220.00 PSI | 400' Vertical Dynamic Lift head to Hilltop Reservoirs | ● Live Stream |
Interactive Operator Simulation & Telemetry Override
Member Controls
Test pump responses, float switches, and visual flow piping
Click to Expand/Collapse
Pumps Operating State
Well Pump (WP-01)
Transfer Pump (TP-01)
Lift Pump (LP-01)
Lower Tank 1 & 2 Floats
Tank 1 (Lower Raw)
Tank 2 (Settling / Feed)
Upper Tanks & Overflow
Tank 3 (Primary Receiving)
Tank 4 (Full Sensor)